Grid Single Phase Source with source impedance model using RL branch based on short circuit level or transformer capacity & impedance.
Grid Single Phase Source with source impedance model using RL branch.
User can define the grid source line voltage, frequency, transformer power capacity, transformer impedance, short circuit level and X/R ratio to determine the source impedance, R and L.
Determine R & L based on transformer power capacity and transformer impedance
Zbase = Vrms^2/S;
Z = Zbase * (ZTx/100);
R = Z/sqrt(1+X_R^2);
L = (R*X_R)/(2*pi*f0);
Determine R & L based on 3 phase short circuit level at base voltage
XL = Vrms^2/SC;
R = XL/X_R;
L = XL/(2*pi*f0);