Three Phase dynamic load

17 views (last 30 days)
andre albagli
andre albagli on 23 Mar 2015
Commented: jun on 26 Jun 2024
Guys:
I´m an electric engineering student and I´m trying to create a IEEE-33 distribuion line topology with simulink as shown in figure 1. Source voltage is 138Kv and transformer reduces to 13.8 Kv.
Instead of using fixed loads, I´m using three phase dynamic load with external control as show in figure 2.
I´m facing a problem with with a very small model with three loads. Voltages and currents that are associated to these load models as show in figure 3 have strange behaviours. Results are like numeric noise. I was suspecting that the problem could be related with solve model but I tried fixed step and variable step with the same results.
Can anyone explain to me what is going on with the model and how to fix it ?
Sincerely, Andre Nudel
  1 Comment
Atieh Delavari
Atieh Delavari on 26 Aug 2015
Edited: Atieh Delavari on 26 Aug 2015
Hi I think you should adjust configuration parameters to see better waves forms

Sign in to comment.

Answers (2)

Sebastian Castro
Sebastian Castro on 24 Mar 2015
It could very well be numerical noise. I noticed you are still using the ode45 solver, which is the default for Simulink.
If you open up Model Configuration Parameters, and go to the Solver pane, try:
  1. Change the solver to "ode23tb"
  2. Change the Relative Tolerance parameter from "auto" to "1e-4"
Both of these constitute the recommended settings for SimPowerSystems models, as shown in the power_new function.
If you still get noise, try further reducing the Relative Tolerance and Absolute Tolerance parameters, as well as the Max step size. This may help further.
- Sebastian
  1 Comment
andre albagli
andre albagli on 24 Mar 2015
Sebastian :
Thanks for your answer. I´ll do it straightaway and let you know.
Thanks! Andre

Sign in to comment.


andre albagli
andre albagli on 24 Mar 2015
Sebastian:
I tried to change these parameters but the results are the same. Any other sugestion ?
  5 Comments
jun
jun on 26 Jun 2024
Hello, I recently encountered a similar issue and found that the aforementioned method did not solve the problem. I added a three-phase circuit breaker in front of the Three-Phase Dynamic Load. After opening the circuit breaker, there was still significant voltage fluctuation at the front end of the breaker. I set the line voltage to 400V, but the actual voltage exceeded 100,000V. I found that the issue does not occur when no active and reactive power parameters are input for the load.

Sign in to comment.