wrong reactive power in “one machine infinite bus" system

16 views (last 30 days)
according to the exmaple the generator should produce 156 MVar reactive power, but instead in my simulink model the infinite bus provides the most part of reactive power, really don't know where is the mistake...

Answers (1)

Sabin
Sabin on 23 Jul 2025
The attachment is invalid. Double-check the generator’s voltage control settings and ensure that the reference voltage and limits are set appropriately so the generator can supply the required 156 MVar, rather than relying on the infinite bus for reactive power support.