2P-MA Heat Exchanger Block Not Stable

2 views (last 30 days)
Hi, I have recently attempted to implement the 2P-MA heat exchanger block in the Simscape Fluids toolbox and the results were very unstable.
For the first case, where it is used as an evaporator, it seems fine.
For the second case, where it is used as a condenser, the results were constantly fluctuating.
What is causing this problem? I have checked the mathematical model given on the webpage and that does not seem to be the issue here.
On a side note, were these component models validated using experimental data?

Accepted Answer

Juan Sagarduy
Juan Sagarduy on 26 Oct 2020
Hello Tech
When looking at your diagram, i believe that the model is over-constrained on both 2p and MA end sides. You should prescribe the conditions at the inlet of both 2P and MA as u did, but the conditions at the outlet will be determined by the heat exchanged. It is quite difficult to set the thermodynamic conditions consistently.
Hope this helps Br Juan
  2 Comments
Tech Logg Ding
Tech Logg Ding on 27 Oct 2020
Dear Juan,
Thank you very much for your reply. Just to follow up on that, how can I leave the outlets unconstrained? What block would you recommend for that?
Thank you.
Regards,
Ding
Juan Sagarduy
Juan Sagarduy on 31 Oct 2020
Try with simple reservoirs on both outlets with atmospheric pressure. Let the gas and 2-phase fluid circulate and exchange heat.
The enthalpy on the sinks should converge to the values you expect, as well as the vapor quality become low.
If not then flow values or heat exchanger parameters need to be reviewed.
My 2c / Juan

Sign in to comment.

More Answers (0)

Categories

Find more on Simscape Fluids in Help Center and File Exchange

Products


Release

R2020a

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!